Trading Engineers logo
Tools

Fire pump package builder.

Enter building type, floors and sprinkler count — get NFPA 20 / IS-compliant flow + head + 3-pump package (electric main + diesel standby + jockey).

  • NFPA 20
  • IS 15105
  • Kirloskar FR-series
  • Wilo fire pumps
Inputs
Result
Design flow
17,000 LPM
1020 m³/hr — sprinkler + hydrant allowance
Total head
98 m
15 floors × 3.5 m + residual + friction
Package configuration
3-pump skid
Split-case electric main + Diesel standby (same flow/head) + Jockey pump (30 L/min @ full head)
Brand recommendation
Kirloskar FR-series
NFPA 20 / IS 15105 compliant

These are indicative figures for quick sizing. Our engineers confirm every number on site with a load study or duty-point verification.

Submit your building + sprinkler layout.

We'll return a full pump package with controllers, pressure vessel and commissioning.